Inspection of Oxy Acetylene Equipment

Inspection of Oxy-Fuel Gas Equipment


Inspection of Oxy Acetylene Equipment
Inspection of Oxy-Acetylene Equipment


 

Requirements for testing

Introduction-By the Australian Standard AS 4839 all oxygen /LPG or acetylene equipment used in RailCorp must be inspected and tested regularly. The inspection must be undertaken by a technically competent person. Oxy and LPG gas equipment used in aluminothermic welding is specialized equipment.

The combination of the regulator, flashback arrestor, non-return valve, cutting attachment, handpiece, mixer, and quick-release hose couplings operate as a unit and should be tested to meet requirements RailCorp has established as necessary to provide
satisfactory aluminothermic welds.


Accordingly, RailCorp has established the following requirements

 

Requirements for testing

1. All equipment is to be inspected and tested once (1) per year

2. Flashback Arrestors are to be replaced every 5 years

3. Welders are to visually inspect equipment before use

4. All equipment is to be tagged with a sticker that displays the following
information:
* Date inspected
* Equipment Identifier
*Name of the inspector?

5. A cable tie is to be placed on all hoses to identify tested hoses. The color of the
cable tie will indicate the year of testing. A cycle of 5 years will be adopted

* 2008 - grey
*2009 - blue
* 2010 – red
* 2011 - green
* 2012 - yellow
* 2013 - grey
* 2014 - blue

6. The following RailCorp personnel are competent and are to conduct the testing

* John Mason
* Stephen Maddock

Leak and function testing procedure

This test procedure covers the following equipment:

1. Regulators
2. Hoses

3. Blowpipe
4. Cutting attachment
5. Flashback arresters

Test equipment required

1. Gas supply
2. Water tank
3. Lead Detector
4. Blanking off type 40 cutting nozzle
5. Blanking off the tip
6. Setting gauge RT 611 & RT 612
7. Hose blanking plugs
8. Flashback arrester test unit

 

Testing Set-Up

1. Connect all system components.
2. Connect the regulator to the gas supply.
3. Connect FBA to the outlet of the regulator.
4. Connect a hose to the blowpipe.
5. Repeat for other gas supplies.
6. Connect the mixer or cutting attachment to the blowpipe.
7. Fit cutting tip.
Note: Ensure all connections are tight using an appropriate spanner.

General Leak Test

1. Ensure the regulator pressure adjusting knob is turned fully anti-clockwise.
2. Blowpipe valves are fully closed.
3. Open the cylinder gas supply valve slowly.
4. Observe the regulator's low-pressure gauge.
If pressure registers on a low-pressure gauge (creep), this indicates a faulty
regulator and it must be replaced

5. Screw in the regulator pressure adjusting knob.
6. Set pressure to 100 kph.
7. Repeat for other gas supplies.
8. Close cylinder gas supply valves.
9. Observe regulator pressure gauges (nominal 1 minute).
If a pressure drop is observed, there is a leak in the system.


Specific leak test Regulator

1. Disconnect the hose and flashback arrester from the regulator.
2. Blank off the regulator outlet( use RT610 or RT611).
3. Pressure regulator to 100 kph.
4. Check for leaks using a suitable leak detection liquid.
5. Check for leaks at:
6 Gas cylinder supply valve and regulator connection
7 Regulator inlet and body connection
8 Regulator outlet and body connection
9 Pressure gauge and body connections
10 Hose connection

Hose Pipe

1. Disconnect the hose from the blowpipe.
2. Blank off the hose end.
3. Pressure hose to 100 kph.
4. Check for leaks using a suitable leak detection liquid.
5. Check for leaks at hose connections.


Blowpipe control valves

1. Connect the blowpipe to the hose.
2. Pressurise to 100 kph.
3. Immerse the welding tip in clean water.
If bubbles appear from the tip end, this indicates leaking control valve seats and the
blowpipe must be repaired or replaced.
Cutting attachments control and cutting oxygen valve
1. Connect the cutting attachment to be tested to a tested blowpipe.
2. Pressurise to 100 kph

3. Immerse the nozzle in clean water.
If bubbles appear from the nozzle end, this indicates leaking control valve seats and
the blowpipe must be repaired or replaced.
Blowpipe
1. Fit the mixer to the blowpipe.
2. Fit the blanked-off tip to the mixer.
3. Pressurise to 100 kph.
4. Open the blowpipe of all control valves fully.
5. Immerse the whole assembly in clean water.
6. Check for leaks at:
7. Hose connections
8. Control valve gland nuts
9. Mixer to blowpipe connection
10. Brazed joints


Cutting attachment
1. Fit cutting attachment to the tested blowpipe.
2. Fit the blanked-off nozzle to the cutting attachment.
3. Pressurise to 100 kph.
4. Open blowpipe control valves fully.
5. Immerse the whole assembly in clean water.
6. Operate the cutting attachment lever.
7. Check for leaks at:
8 Control valve gland nut
9 Cutting attachment to blowpipe connection
10 Cutting oxygen valve
11 Nozzle nut
12 Brazed joints

Regulator Seat inter-leak test.

1. Connect the setting gauge to the regulator outlet (TR610 & RT611).
2. Ensure the regulator pressure-adjusting knob is turned fully anti-clockwise.
3. Open the cylinder gas supply valve slowly.

 

 

Post a Comment

0 Comments